| Type | mini-pleat absolute filter |
| Frame | galvanized steel or aluminium |
| Filter media | glass fiber paper |
| Separators | continuous thermoplastic cord |
| EN 779 Class | H10-H14 |
| DOP Efficiency | 95%-99.999% |
| MERV | MERV 11-15(ASHRAE 52.2-1999) |
| DIN 53438 Flammability | F1 |
| UL 900 Standard | CLASS 2 |
| Final pressure drop | (recommender) 500Pa |
| Max. air flow rate | 125% of nominal air flow rate |
| Max. operating temperature | 60℃ |
| Max. relative humidity | 80% |
| Applications | fine particle filtration for clean room |
|
Type |
Class |
DOP Efficiency |
Dimensions |
Filtering surface (m2) |
Rated air flow (m3/h) |
Initial pressure drop (Pa) |
||
|
Length (mm) |
Height (mm) |
Depth (mm) |
||||||
|
WGG-12 |
H12 |
99.95% |
610 |
610 |
50 |
7 |
450 |
110 |
|
WGG-12 |
H12 |
99.95% |
610 |
610 |
70 |
10 |
600 |
110 |
|
WGG-12 |
H12 |
99.95% |
610 |
610 |
90 |
14 |
900 |
110 |
|
WGG-14 |
H14 |
99.995% |
610 |
610 |
50 |
7 |
450 |
130 |
|
WGG-14 |
H14 |
99.995% |
610 |
610 |
70 |
10 |
600 |
130 |
|
WGG-14 |
H14 |
99.995% |
610 |
610 |
90 |
14 |
900 |
130 |